Gongyi, Henan, China Mon–Sat 08:30–18:00 GMT+8 +86 198 0207 6850
Power fittings — Terminal connector

Aluminium terminal connectors for crews without a press

The same conductor-to-equipment joint as a lug, made with a spanner instead of a crimping tool. Re-openable, suitable for live work, and honest about where torque discipline has to come from.

Bolted
Pressure plate
Spanner
Installation tool
Re-openable
For testing
GB/T 2314
Fitting standard
Request a quote WhatsApp Reply within one working day
Short answer

An aluminium terminal connector — a bolted equipment connector — makes the same joint as a cable lug with a spanner instead of a press. A pressure plate clamps the conductor onto a palm that bolts to the equipment terminal. It is the right choice where there is no crimping tool, where the joint must be re-openable for testing, or where the work is done live. The trade-off is that contact pressure depends on bolt torque, so torque and re-torquing become part of the maintenance schedule.

The choice that actually matters

Half the enquiries we get for a "terminal connector" are really enquiries for a lug, and the other half are the opposite. The decision is not commercial — it is about what the crew can do on site and what the specification allows.

Bolted connector against compression lug
QuestionBolted terminal connectorCompression lug
Tool neededSpanner or torque wrenchPress and matched die
Site conditionsWorks in rain, cold, confined spacesNeeds a clean, dry, stable setup
Re-openableYes — unbolt and inspectNo — cut off and remake
Live workPossible with a hot stickNot possible
ConsistencyDepends on torque disciplineDepends on die and press condition
Long-term riskTorque decay, loosening under vibrationOxide and under-crimping
Current pathThrough the clamp interfaceThrough a cold-welded barrel

Neither is better in the abstract. A utility that specifies compression is buying consistency; one that specifies bolted is buying maintainability. We make both, so the recommendation follows the specification rather than the margin.

What decides whether it fits

The palm is the part that has to match the equipment, and the groove is the part that has to match the conductor. Both are dimensional, and neither can be read off a photograph.

On the palm side: hole spacing, stud diameter, pad width, and whether the palm is flat or angled — an angled palm is often the only way to land on a terminal that faces sideways in a crowded box. On the conductor side: the outside diameter of the cable or the bare conductor, the number of conductor clamps (one or two), and whether the conductor is bare or insulated.

Two details decide whether the joint stays tight: the bolt grade and the locking method. A spring washer alone is not a locking device under thermal cycling; a Belleville washer or a specified torque-plus-angle procedure is. State which one your standard requires.

Materials and finish

Bodies are wrought aluminium, machined from bar or extruded, with the palm drilled to your pattern. Bolts are galvanised steel or stainless, chosen against the corrosion class of the site rather than by habit — a stainless bolt in an aluminium body is a galvanic pair of its own, which is why the specification usually asks for galvanised with an anti-seize compound.

Tin plating is available on request for coastal and substation work, and it is worth having on the conductor groove as well as the palm: that is where the oxide problem lives.

FAQ

Buyer questions

Still unresolved? Send the question with your drawing — we answer in writing, not in a sales call.
What is the difference between a terminal connector and a cable lug?

The installation method. A lug is crimped with a press and a matched die; a terminal connector is bolted with a pressure plate. They do the same electrical job and are not interchangeable in a specification that names one of them.

Can it be installed live?

With the right hot stick and a connector designed for it, yes — that is one reason utilities keep bolted connectors in the stores. Tell us if live work is intended and the palm and bolt layout has to suit the stick fitting.

How often does it need re-torquing?

According to the utility's maintenance schedule, not ours. What we can do is state the torque and supply the locking method the specification asks for. Aluminium creeps under clamp load, so a re-torque interval after the first thermal cycles is normal practice, not a defect.

Do you make two-conductor and angled versions?

Yes, both are quoted against the drawing — the palm pattern changes, the process does not.

Which standard applies?

GB/T 2314 for the fittings themselves, with IEC 61238-1 or ANSI C119.4 as the heat-cycle test basis depending on the market. Say which one your utility applies and the report pages follow the quotation.

Send the palm pattern and the conductor OD.

Hole spacing, stud size and whether the palm has to be angled — that is what decides the part.

Request a quote WhatsApp